Specifications
4 Communication settings and guide of HMI connecting with controller
Step Coil
SC 0-2047
------
DDDD
Step Contact
SS 0-2047
------
DDDD
Timer Coil
TC 0-2047
------
DDDD
Timer Contact
TS 0-2047
------
DDDD
Link Relay
B 0-1FFF
B 0-1FFF
HHHH
Edge Relay
V 0-2047
------
DDDD
Annunciator
F 0-2047
------
DDDD
Latch Relay
L 0-8191
------
DDDD
Special Internal Relay
SM 0-2047
------
DDDD
Internal Relay
M 0-8191
------
DDDD
Output Relay
Y 0-1FFF
Y 0-1FFF
HHHH
Input Relay
X 0-1FFF
X 0-1FFF
HHHH
File Register
------
ZR 0-393216
DDDDDD
File Register
------
R 0-32767
DDDDD
Index Register
------
Z 0-19
DD
Counter Value
------
CN 0-1023
DDDD
Retentive Timer Value
SN 0-2047
DDDD
Timer Value
------
TN 0-2047
DDDD
Special Link Register
------
SW 0-7FF
HHH
Link Register
W 0-1FFF
HHHH
Special Data Register
------
SD 0-2047
DDDD
Data Register
------
D 0-45055
DDDDD
Q03UDE
Device Bit Address Word Address Format Notes
Direct output
DY 0-1FFF
HHHH
Direct input
DX 0-1FFF
HHHH
Step Relay
S 0-8191
------
DDDD
Special Link Relay
SB 0-7FF
SB 0-7F0
HHHH
Counter Coil
CC 0-1023
------
DDDD
Counter Contact
CS 0-1023
------
DDDD
Step Coil
SC 0-2047
------
DDDD
Step Contact
SS 0-2047
------
DDDD
Timer Coil
TC 0-2047
------
DDDD
Timer Contact
TS 0-2047
------
DDDD
Link Relay
B 0-1FFF
B 0-1FF0
HHHH
Edge Relay
V 0-2047
------
DDDD
Annunciator
F 0-2047
------
DDDD
- 221 -