Specifications

4 Communication settings and guide of HMI connecting with controller
D8120 Communication format
D8121 Station number
D8129 Overtime
For example
The communication parameters of PLC as follow:
Communication format: 9600bps, 7, even, 2;
Station No.:1;
H/W type: RS485;
Time out: 1
Set the value of D8120/D8121/D8129:
D8120=0xE08E
D8121=1
D8129=1
NOTE: Restart the PLC after setting the value of D8120.
FX2N-10G/20GM protocol
Default communication: 9600, 8, even, 1; station: 0
RS232 communication
RS422 communication