Specifications
4 Communication settings and guide of HMI connecting with controller
The Slot No. is the I/O slot position where the communication module is. For example, G6L-CUEC is
plugged in the I/O 1, the Slot No. should be selected SLOT 1.
NOTE: Be sure to put the switch of the module to 9 (ON-LINE) position when communicating.
LS ig5A Protocol
HMI Setting
Default communication: 9600bps,8,none,1;PLC station:1
PLC Setting
Settings
Parameter directions
panel display
Addr
I59
A43B Protocol
0
Modbus RTU
1
LS BUS
I60
A43C Station
1-250
I61
A43D Baud Rate
0 1200[bps]
1 2400[bps]
2 4800[bps]
3 9600[bps]
4 19200[bps]
I65
A441 Parity Check
0
none
,
stop bit:1
1
none
,
stop bit:2
2
even
,
stop bit:1
3
odd
,
stop bit:1
The controller also supports the standard Modbus RTU protocol , set the agreement with
LS ig5A.
◎Ethernet Communication Setting
LS GLOFA FEnet protocol
GM6-CPU Setting
- 167 -