Specifications
4 Communication settings and guide of HMI connecting with controller
NOTE: the address of DP can’t be the same as MPI’s. Double click the address number to change.
(4)Double click “GATEWAY"->"eview"->"B_MO1"to extend device.
NOTE: for project configuration of BRIDGE, you must configure DI/D0 resource of 12 bytes firstly.
AI/AO is optional.
(5)Must Use OB82,OB86,OB100,OB121,OB122 in the ladder program of the external device, otherwise
you need to manually operate the RUN switch of the external device as “RUN,STOP,RUN” in this order
upon restart the display or PLC. When you use those special OB block, the communication will be
automatically recovered even if you restart the display or PLC.
(6)Save and compile, and download to module, then the light of profibus is on.
(7)After configuration, and then you can program.
Bus Bridge setting:
- 137 -