Specifications
38
I-T-E TELEMAND
(R)
Electric Motor Operator
General
The motor operated mechanism is designed to open, close
and reset a circuit breaker or switch by remote control. The
customer must supply the circuit breaker or switch, normally
ON and OFF momentary type push-buttons, external wiring,
a control power source, and all control logic. Consult the
wiring diagram (Figure 3, page 40) for a typical control
connection.
The motor operator is hinged for opening to the left or right
dependent on catalog number designation. The āLā suffix
means the motor operator is hinged to the left. A motor
operator hinged to the right uses no suffix.
NOTE: For automatic reset operation a separate auxiliary
contact must be provided by the customer See page 40
for more details.
Operator Selection
Motor
Operator
Frame For Use With I-T-E
Circuit Breakers
MOJ6120
MOJ6120L
MOJ6240
MOJ6240L
JD,LD
SJD6, SLD6,
SHJD6, SHLD6,
SCJD6, SCLD6
Installation
A. Turn off and lock out all power supplying circuit breaker
and motor operator before installing or servicing.
B. Attach the circuit breaker to its mounting surface using
the mounting hardware (1) supplied with the motor
operator (Figure 2).
C. Remove the four shield screws (2) and two lug shields (3)
(Figure 1).
D. Replace the shields with those provided with the motor
operator and discard the shields which were removed.
E. Open the motor operator cover and attach the motor
operator to the circuit breaker using the spacers (4) and
screws (5) provided (Figure 2).
Figure 2
Figure 2