Specifications

30
I-T-E Rotary Handle
Enclosure Mechanism
Types 1, 12
Variable Depth (D11CJU2)
General
Handle with permit locking the disconnect device in the OFF
position using up to three locks having shackles up to 3/8 in.
in dia. Provision for locking in ON position is provided/ but the
handle plate must have the material covering the locking
notch removed. This can be done with a hacksaw or file. The
handle has a voidable interlock. Voiding the interlock requires
inserting a small screwdriver into the rectangular opening in
the handle plate, which will release the handle.
A. Measure distance F from breaker mounting surface to
top surface of cover. If distance F is less than 8 in. then
remove shaft guide bracket.
B. Find length G by subtracting 5.50 in. from F dimension.
Mark length G from underside of operating plate on shaft
and cut shaft squarely at mark.
NOTE: Breaker must be “tripped” during installation. Push red
button marked PUSH TO TRIP (1).
C. Loosen the two 8-32 screws (2) that secure both terminal
shields to the breaker, remove the two .28 in. dia.
knockouts (3) and fasten circuit breaker with four 3.56
total length fastening members (4). Wire circuit breaker
and replace terminal shields. Using 1/4-20 x 11/2 in. R.H.
screws together with lockwasher and washer supplied
with kit, attach mechanism plate assembly on breaker as
shown.
D. Insert end of operating shaft into square socket in cast
operating arm so that top of shaft has proper relationship
to handle as illustrated in photograph on front of instruc-
tion sheet. (Breaker or handle may be rotated in 90
increments so long as relationship of handle and top of
operating shaft is held.) Tighten set screw in side of cast
operating arm (recommended torque—75 in. Ib.).
Handle Mounting
Holes in cover to be as shown in Figure 2. Mount handle with
cork gasket on cover and handle mounting plate on inside of
cover. Fasten together loosely through cover with the two
short screws provided. The two .31 in. dia. mounting holes
must be rotated in the same 90ø increments to maintain the
handle and operating shaft relationship. Close cover, adjust
handle with actuator to be free of binding. Tighten handle
mounting screws and operate handle ON and OFF to see that
circuit breaker operates satisfactorily.