Specifications

22
I-T-E Pressure Wire Connectors
General
Each connector kit contains a solderless connector and
associated hardware for making one line or load connection.
Installation
NOTE: Trip unit must be installed in circuit breaker prior to
mounting load end connector.
A. Tighten mounting screws (1) to securely attach connec-
tor. See table for torque values.
B. Tighten set screws (2) securely to prevent overheating of
conductor and connector. See table for torque values.
Connector(2)
Catalog Numbers
Circuit Breaker
Ampere Rating
Connector Wire Range
Set Screw
Torque (in. Ib.)
Mounting
Screw Torque
(in. Ib.)
For Use With
Type(s)
TA2J6500
200-600
(1-2)#3/0-500 MCM(Cu)
(1-2)#4/0-500 MCM (Al)
300 132
SJD6,SLD6,
SHJD6,SHLD6,
SCJD6,SCLD6
TA1L6750
200-600
(1)#500-750 MCM (Al)
200-600(1)#500-600 MCM(Cu)
or
2Pcs.of250 MCM (Al)
500 228
TC1J6600
200-600 (1)#3/0-600 MCM(Cu) 500 228
TC2J6500
200-600 (1-2)#3/0-500 MCM(Cu) 300 132
Figure 1