Specifications

20
I-T-E Plug-In Adapters
General
A complete plug-in installation requires one line end adapter
assembly (consisting of a mounting block, tulip connectors
and associated hardware), one load end adapter assembly
and one switchboard mounting plate. The switchboard
mounting plate is optional and can be replaced by other
mounting means to suit customer’s requirements.
Application Information
Breaker Type No. Of
Poles
Line End
Adapter
Cat No.
Load End
Adapter
Cat No.
Switchboard
Mtg Plate
Cat. No.
SJD6,SHJD6 2 PC5777 PC5777 PL5796
3 PC5778 PC5778 PL5796
SLD6,SHLD6 2 PC5660 PC5660 PL5796
3 PC5661 PC5661 PL5796
SCJD6 2 PC5660 PC5660 PL5797
3 PC5661 PC5661 PL5797
SCLD6 2 PC5660 PC5660 PL5797
3 PC5661 PC5661 PL5797
Mounting Preparation (Figures 1 and 2)
A. If the switchboard mounting plate (PL5796, PL5297) (1)
is to be used, provide drilling as shown in Figure 1.
B. If other mounting means are to be used, provide the
cutouts and drilling required to mount the adapter blocks
as shown in Figure 2.
Switchboard Mounting Plate, if used (Figure 3)
A. Place switchboard mounting plate (1) in position at
location previously prepared in Step A above. Secure in
place with 5/16 in Lockwashers (3) and 5/16 in. bolts (4)
furnished.
Mounting Block (Figure 3)
A. Align mounting block (2) with cutouts in switchboard
mounting plate (or customer’s mounting means as
previously prepared in Step B above) and secure in
place with 5/16 in. lockwashers (3) and 5/16 in. bolts (4)
furnished .
Breaker Preparation (Figure 4)
A . Remove pressure wire connectors from breaker if present.
Place tulip clip assembly (5) on back of breaker in recess
provided in base molding. Secure in place with 1/4 in.
Belleville washers (6) and 1/4 in.-20 x 1 hex head bolts
(7) furnished. Recommended tightening torque for these
bolts is 5-6 ft. Ib. to assure a good electrical connection.
Repeat this procedure for the remaining tulip clip assem-
blies.
B. Insert line end shields (8) into slots provided at line and
load end of breaker No lower end shields are required.
C. Affix accessory warning labels (9) to top of breaker as
indicated in Figure 5.
Final Assembly (Figure 6)
A. Make bus connections to flat bar connectors at rear of
mounting blocks with customer supplied 5/16 in. hard-
ware (see Figure 6 for hole pattern).
Caution: Make certain that breaker operating handle is in the
OFF position before proceeding with the next step.
B. Align breaker with mounting blocks and force female
tulip clips over male studs in mounting blocks until
breaker base bottoms against mounting block. Secure
breaker in place with ‘/4-20 x 3 in. mounting screws (10),
lockwashers (11) and flatwashers (12) furnished.
C. If installation requires use of front panel trim, provide
cutout for breaker escutcheon (Figure 7).