Specifications

JD and LD-Frame Trip Adjustments
9
Continuous Current (I,) and Long Time Delay
All models have a Continuous Current and Long Time Delay
adjustment. This single knob adjusts the Continuous Current
setting of the circuit breaker and sets the Long Time Delay.
This setting (I,) is a percentage of the Maximum Continuous
Current rating (In) Two long time delay bands are available.
These are delay times of 3 seconds or 25 seconds at 6 times
the Continuous Current Setting (Ir) These are selected by
using the appropriate area of the setting.
Instantaneous Pickup
All models have an instantaneous Pickup adjustment. This
adjustment sets the instantaneous Pickup of the circuit
breaker. The settings are multiples of the Continuous Current
Setting (I,).
These devices have a fixed instantaneous override of ap-
proximately 10.5 times the Maximum Continuous Current
rating (In) of the circuit breaker. When set to “MAX” the
Instantaneous Pickup defaults to the instantaneous override
value.