ISGS Settings Worksheet for Date: Set A
S-8 Siemens Energy & Automation, Inc.
3000 Alarm Setpoints
3100 Demand Setpoints
3101 Demand Interval 15 30 60 minutes
3102 Sync time 0 15 30 45 minutes after hour
3103 Subperiods 60 1 234612
3104 Subperiods 30 1 236
3105 Subperiods 15 1 3
3106 Current Average Demand Enabled Disabled
3107 Current Average Demand Pickup 3000 A Range: 0-9999 A (1 A steps) A
3108 KW Demand Enabled Disabled
3109 KW Demand Pickup 100000 kW
Range: 0-999,999 kW
(1 kW steps)
kW
3200 Power Setpoints
3201 KVAR Function Enabled Disabled
3202 KVAR Pickup 100000 kVAR
Range: 0-999,999 kVAR
(1 kVAR steps)
kVAR
3203 KVAR Time Delay 1800 s Range: 0-3600 s (1 s steps) s
3204 KVA Function Enabled Disabled
3205 KVA Pickup 100000 kVA
Range: 0-999,999 kVA
(1 kVA steps)
kVA
3206 KVA Time Delay 1800 s Range: 0-3600 s (1 s steps) s
3207 PF Lead Function Enabled Disabled
3208 PF Lead Pickup 0.8 Range: 0.2-1.0 (0.1 steps)
3209 PF Lead Sign Lag Lead
3210 PF Lead Delay 1800 s Range: 0-3600 s (1 s steps) s
3211 PF Lag Function Enabled Disabled
3212 PF Lag Pickup 0.8 Range: 0.2-1.0 (0.1 steps)
3213 PF Lag Sign Lag Lead
3214 PF Lag Delay 1800 s Range: 0-3600 s (1 s steps) s