Operator`s manual

ISGS Settings Worksheet for Date: Set A
S-4 Siemens Energy & Automation, Inc.
A1900 Directional Phase Time Overcurrent (67)
A1901 Function 67 Enabled Disabled
A1902 Curve 67 Inverse Short Inverse Long Inverse
Moderately
Inverse
Custom Very Inverse Extremely Inverse Definite Inverse
Slightly Inverse
I
2
T without Limit
A1903
Pickup 67 5 A CT 0.5 A Range: 0.5-20 A (0.1 A steps) A
1 A CT 0.1 A Range: 0.1-4 A (0.1 A steps) A
A1905 Time Dial 67 0.10 Range: 0.1-9.9 (0.1 steps)
A1906 Filter 67 rms fundamental
A1907 Impedance 67 45° Range: 0-90° (1° steps) °
A1908 Direction 67 Normal Reverse
1910 Freeze Waveform 1 67 on Pickup on Trip None
1911 Freeze Waveform 2 67 on Pickup on Trip None
A2000 Directional Neutral Time Overcurrent (67N)
A2001 Function 67N Enabled Disabled
A2002 Curve 67N Inverse Short Inverse Long Inverse
Moderately
Inverse
Custom Very Inverse Extremely Inverse Definite Inverse
Slightly Inverse
I
2
T without Limit
A2003
Pickup 67N 5 A CT 0.5 A Range: 0.5-20 A (0.1 A steps) A
(PU point is 1.06 1 A CT
of PU setting).
0.1 A Range: 0.1-4 A (0.1 A steps) A
A2005 Time Dial 67N 0.10 Range: 0.1-9.9 (0.1 steps)
A2006 Filter 67N rms fundamental
A2007 Impedance 67N 45° Range: 0-90° (1° steps) °
A2008 Direction 67N Normal Reverse
2010 Freeze Waveform 1 67N on Pickup on Trip None
2011 Freeze Waveform 2 67N on Pickup on Trip None
S
isv3o_1.bk : isv3o_cf.frm Page 4 Wednesday, August 7, 1996 10:51 AM