Operator`s manual
ISGS Settings Worksheet for Date: Set A
Siemens Energy & Automation, Inc. S-3
A1700 Phase Time Overcurrent (51)
A1702
Curve 51 Inverse Short Inverse Long Inverse
Moderately
Inverse
Custom Very Inverse Extremely Inverse Definite Inverse
Slightly Inverse
I
2
T without Limit
A1703
Pickup 51 5 A CT 0.5 A Range: 0.5-20 A (0.1 A steps) A
(PU point is 1.06 1 A CT
of PU setting).
0.1 A Range: 0.1-4 A (0.1 A steps) A
A1705 Time Dial 51 0.1 Range: 0.1-9.9 (0.1 steps)
A1706 Filter 51 rms fundamental
A1709 Reset 51 Disk Emulation Instantaneous
1710 Freeze Waveform 1 51 on Pickup on Trip None
1711 Freeze Waveform 2 51 on Pickup on Trip None
A1712 Block 51 by None 50HS & 50HSN 50HS 50HSN
A1800 Neutral Time Overcurrent (51N)
A1801 Function 51N Enabled Disabled
A1802
Curve 51N Inverse Short Inverse Long Inverse
Moderately
Inverse
Custom Very Inverse Extremely Inverse Definite Inverse
Slightly Inverse
I
2
T without Limit
A1803
Pickup 51N 5 A CT 0.5 A Range: 0.5-20 A (0.1 A steps) A
1 A CT 0.1 A Range: 0.1-4 A (0.1 A steps) A
A1805 Time Dial 51N 0.1 Range: 0.1-9.9 (0.1 steps)
A1806 Filter 51N rms fundamental
A1809 Reset 51N Disk Emulation Instantaneous
1810 Freeze Waveform 1 51N on Pickup on Trip None
1811 Freeze Waveform 2 51N on Pickup on Trip None
A1812 Block 51N by None 50HS & 50HSN 50HS 50HSN
S
isv3o_1.bk : isv3o_cf.frm Page 3 Wednesday, August 7, 1996 10:51 AM