Operator`s manual
ISGS Settings Worksheet for Date: Set A
S-2 Siemens Energy & Automation, Inc.
A1500
Instantaneous Phase Overcurrent (50)
High-Set Instantaneous Phase Overcurrent (50HS)
A1501 Function 50 Enabled Disabled
A1502
Pickup 50 5 A CT 1.0 A Range: 1-120 A (0.1 A steps) A
1 A CT 0.2 A Range: 0.2-24 A (0.1 A steps) A
A1504 Time Delay 50 0.00 s Range: 0-60 s (0.01 s steps) s
1510 Freeze Waveform 1 50 on pickup on Trip None
1511 Freeze Waveform 2 50 on pickup on Trip None
A1512 Block 50 by None 50HS & 50HSN 50HS 50HSN
A1551 Function 50HS Enabled Disabled
A1552
Pickup 50HS 5 A CT 5.0 A Range: 5-120 A (0.1 A steps) A
1 A CT 0.2 A Range: 0.2-24 A (0.1 A steps) A
1560 Freeze Waveform 1 50HS --- on Trip None
1561 Freeze Waveform 2 50HS --- on Trip None
A1600
Instantaneous Neutral or Ground Overcurrent (50N)
High-Set Instantaneous Neutral or Ground Overcurrent (50HSN)
A1601 Function 50N Enabled Disabled
A1602
Pickup 50N 5 A CT 1.0 A Range: 1-120 A (0.1 A steps) A
1 A CT 0.2 A Range: 0.2-24 A (0.1 A steps) A
A1604 Time Delay 50N 0.00 s Range: 0-60 s (0.01 s steps) s
1610 Freeze Waveform 1 50N on Pickup on Trip None
1611 Freeze Waveform 2 50N on Pickup on Trip None
A1612 Block 50N by None 50HS & 50HSN 50HS 50HSN
A1651 Function 50HSN Enabled Disabled
A1652
Pickup 50HSN 5 A CT 5.0 A Range: 5-120 A (0.1 A steps) A
1 A CT 0.2 A Range: 0.2-24 A (0.1 A steps) A
1660 Freeze Waveform 1 50HSN --- on Trip None
1661 Freeze Waveform 2 50HSN --- on Trip None