Operator`s manual
ISGS Settings Worksheet for Date: Set B
S-22 Siemens Energy & Automation, Inc.
B2400
Phase Sequence Voltage (47)
Negative Sequence Voltage (47N)
B2401 Function 47 Enabled Disabled
2410 Freeze Waveform 1 47 Settings displayed or changed here apply to both parameter sets
2411 Freeze Waveform 2 47 Settings displayed or changed here apply to both parameter sets
B2451 Function 47N Enabled Disabled
B2452 Curve 47N Inverse Definite Inverse
B2453 Pickup 47N 10% Range: 4-40% (1% steps) %
B2454 Time Delay 47N(Defin.) 0.00 s
Range: 0-100 s (0.01 s steps),
or
∞
s
B2455 Time Dial 47N (Inverse) 0.1 Range: 0.1-9.9 (0.1 steps)
B2456 Maximum Time (Inverse) 120 s Range: 1-250 s (1 s steps) s
B2457 Block 47N by 40 V Range: 40-120 V (1 V steps) V
2460 Freeze Waveform 1 47N Settings displayed or changed here apply to both parameter sets
2461 Freeze Waveform 2 47N Settings displayed or changed here apply to both parameter sets
B2500
Overfrequency (81O)
Underfrequency (81U)
B2501 Function 81O Enabled Disabled
B2502 Pickup 81O 62.0 Hz
Range: 60.1-65.0 Hz
(0.1 Hz steps)
Hz
B2504 Time Delay 81O 0.10 s
Range: 0-100 s (0.01 s steps),
or
∞
s
2506 Block 81O 40 V Range: 40-120 V (1 V steps) V
2510 Frz. Wfm1 81O Settings displayed or changed here apply to both parameter sets
2511 Frz. Wfm2 81O Settings displayed or changed here apply to both parameter sets
B2551 Function 81U Enabled Disabled
B2553 Pickup 81U 58.0 Hz
Range: 55.0-59.9 Hz
(0.1 Hz steps)
Hz
B2554 Delay 81U 0.10 s
Range: 0-100 s (0.01 s steps),
or
∞
s
B2556 Block 81U 40 V Range: 40-120 V (1 V steps) V
2560 Freeze Waveform 1 81U Settings displayed or changed here apply to both parameter sets
2561 Freeze Waveform 2 81U Settings displayed or changed here apply to both parameter sets
S
isv3o_1.bk : isv3o_cf.frm Page 22 Wednesday, August 7, 1996 10:51 AM