Operator`s manual
ISGS Settings Worksheet for Date: Set B
Siemens Energy & Automation, Inc. S-21
B2200 Overvoltage (59)
B2201 Function 59 Enabled Disabled
B2202 Curve 59 Inverse
Moderately
Inverse
Very Inverse Definite Inverse
B2203
Pickup Source Voltage 59
(if VT mode is (L-N)
Line-to-Line Line-to-Neutral
B2204 Pickup 59 130 V Range: 60-250 V (0.1 V steps) V
B2205 Time Delay 59 (Definite) 0.10 s
Range: 0-60 s (0.01 s steps),
or
∞
s
B2206 Time Dial 59 (Inverse) 0.1 Range: 0.1-9.9 (0.1steps)
2210 Freeze Waveform 1 59 Settings displayed or changed here apply to both parameter sets
2211 Freeze Waveform 2 59 Settings displayed or changed here apply to both parameter sets
B2300 Undervoltage (27)
B2301 Function 27 Enabled Disabled
B2302 Curve 27 Inverse
Moderately
Inverse
Very Inverse Definite Inverse
B2303
PU Source V 27
(if VT mode is (L-N)
Line-to-Line Line-to-Neutral
B2304 Pickup 27 50.0 V Range: 40-230 V (0.1 V steps) V
B2305 Time Delay 27 (Definite) 0.10 s
Range: 0-60 s (0.01 s steps),
or
∞
s
B2306 Time Dial 27 (Inverse) 0.1 Range: 0.1-9.9 (0.1 steps)
2310 Freeze Waveform 1 27 Settings displayed or changed here apply to both parameter sets
2311 Freeze Waveform 2 27 Settings displayed or changed here apply to both parameter sets
S
isv3o_1.bk : isv3o_cf.frm Page 21 Wednesday, August 7, 1996 10:51 AM