Operator`s manual

ISGS Settings Worksheet for Date: Set B
S-20 Siemens Energy & Automation, Inc.
B1900 Directional Time Overcurrent (67)
B1901 Function 67 Enabled Disabled
B1902 Curve 67 Inverse Short Inverse Long Inverse
Moderately
Inverse
Custom Very Inverse Extremely Inverse Definite Inverse
Slightly Inverse
I
2
T without Limit
B1903 Pickup 67 5 A CT 0.5 A Range: 0.5-20 A (0.1 A steps) A
1 A CT 0.1 A Range: 0.1-4 A (0.1 A steps) A
B1905 Time Dial 67 0.1 Range: 0.1-9.9 (0.1 steps)
B1906 Filter 67 rms fundamental
B1907 Impedance 67 45° Range: 0-90° (1° steps) °
B1908 Direction 67 Normal Reverse
1910 Freeze Waveform 1 67 Settings displayed or changed here apply to both parameter sets
1911 Freeze Waveform 2 67 Settings displayed or changed here apply to both parameter sets
B2000 Directional Neutral Time Overcurrent (67N)
B2001 Function 67N Enabled Disabled
B2002 Curve 67N Inverse Short Inverse Long Inverse
Moderately
Inverse
Custom Very Inverse Extremely Inverse Definite Inverse
Slightly Inverse
I
2
T without Limit
B2003 Pickup 67N 5 A CT 0.5 A Range: 0.5-20 A (0.1 A steps) A
(PU point is 1.06 1 A CT
of PU setting).
0.1 A Range: 0.1-4 A (0.1 A steps) A
B2005 Time Dial 67N 0.1 Range: 0.1-9.9 (0.1 steps)
B2006 Filter 67N rms fundamental
B2007 Impedance 67N 45° Range: 0-90° (1° steps) °
B2008 Direction 67N Normal Reverse
2010 Freeze Waveform 1 67N Settings displayed or changed here apply to both parameter sets
2011 Freeze Waveform 2 67N Settings displayed or changed here apply to both parameter sets