Specifications
CP143 H1 / TCP/IP manual Software
Rev. 00/07 5-15
5.6.2 Online
Online parameters must be specifies when functions are to be used that access the module directly
via the network or via the serial interface. Online functions are only available from firmware level
V110 and an NCS V2.1.
The function database <-> CP under Transfer and die functions under Test make use of online
parameters.
The online dialog window provides access to the following settings:
Fig. 5-6:Parameters for online connections
serial
Data is transferred via the serial COM port of your PC to the PG interface of the
CP143 H1 / TCP/IP. You must specify the port no. and the interrupt.
The following are standard settings:
COM1 = Port 3F8 with INT 4
COM2 = Port 2F8 with INT 3 (default)
COM1 = Port 3E8 with INT 4
serial -> H1
Data is transferred via the serial COM port to the PG interface of an H1 module and from
there via the H1 network to a target module identified by means of the respective ethernet
address.
This mode requires specification of the ethernet address of the target module and the serial
parameters (port no. and INT).
TCP/IP
Data is transferred directly via the network to a TCP/IP module. The target module is
specified by means of an IP address.
Please note!
When using TCP/IP you must enter an ethernet ADR 000000000000h.