5.6 Initialization
Every now configuration requires initialization. It is necessary to initialize the identification
parameters as well as H1 and TCP/IP-parameters of the CP143 H1 / TCP/IP-module.
The initialization is not required if you have already loaded a base file. You can find the
initialization functions under menu item Init.
You enter online transfer parameters in the section Online.
5.6.1 CP init
The entry CP-Init under Init places you in an interactive window that provides access to the CP-
base initialization:
Fig. 5-5:CP-base initialization (initial initialization)
Here you must configure the addresses and other identification parameters of the CP.
Before entering a connection, you must also enter a frame base address into this interactive mask.
The entered data is transferred when you depress the Enter key.
Parameters of the CP-initialization
Date, Version
The entries for date and version are for documentation purposes only. You can use these
entries to check at what time a configuration was performed. The version number will
always contain the number associated with the file that is currently loaded.
Name of station
You may specify a name for your base station. The name may consist of a maximum of 19
characters. Station names are used to simplify the configuration of connections. The station
name is important where on-line configurations are concerned.