Specifications
CP143 H1 / TCP/IP manual Commissioning
Rev. 00/07 6-23
Re: 2. Check transport parameters
Normally, transport parameters do not require changing. The dialogue window is displayed so that
the H1 transport parameters may be checked.. Please note, that the transport parameters for all
stations are the same.
Fig. 6-12: Transport-parameter of station 1 and station 2
Re: 3. Configure the connection
Station 1
This example is concerned with H1 connections. From the menu item Verbindungen
(Connections) you must select H1-Transport-Verbindung (H1-transport connection). This will
display the window for TCP connections. Enter the following data for station 1:
• Connection name: SEND to station 2
• Job number: 11
• Priority: 2
• Type of job: SEND
• TSAP local station (ASCII): send
• TSAP remote station (ASCII): receive
• Adr. of remote st.: enter the ethernet-address of station 2.
Fig. 6-13: H1 connection parameters station 1