Specifications

CP143 H1 / TCP/IP manual Software
Rev. 00/07 5-73
5.11.6.3 WriteA-tab
Fig. 5-34: Test program "WriteA" tab
This is where you activate an active write connection
In the same manner as specified for the READ AKTIV-command you must enter the data required
to establish the connection as well as the target module for the data.
Input fields
Remote Host IP-Address of the station to which the data must be written.
Remote Port Connection address of the external station.
Local Port Connection address of the local station. To simplify matters, you may
specify the same address for remote and local.
Time (10mSec) Timer interval for cyclic writes. For cyclic writes the value of the timer
must be at least 5.
OrgKennung Type of target module
DBNo Number of the target module
AnfAdr Start address of the target module
Len Word length of the target module
Control box
UDP Here you may select an unsecured protocol for communicating.
Unsecured communications do not use virtual connections. In this
manner you may select to display only UDP-messages.
Buttons
Connect The connection is established and prepared for the write command.
Write this The data entered into the ASCII fields is written to the CP via the
connection established by the Connect.
Connection data
Target data
Result code of the
write job
ASCII-text that must be
transferred to the CP.
Information on the
connection status and
error messages