Specifications

Position Decoding IP 240
Stipulations
Input card Module address 4
Output card Module address 12
Analog output card Module address 128 (1st output)
IP 240 Module address 144
(IRA enabled for S5-115U and S5-135U
PY 0 enabled for S5-150U)
Data block 10 - Speeds (in binary)
KF+ 1024=maximum forward speed
KF - 1024=maximum backward speed
- Zone limits (BCD code in the range 0 to +99,999)
e.g. DW 15 KH 0003
DW 16 KH 5680
+35,680 beginning of the third and end of the second zone
The initial and final value of a zone enabled in DR 12 must always be
entered: The initial value must be smaller than the final value.
- Bits for the zones used (DR 12)
Bit=Zone Track of the IP 240
0 1 - (Zone 1 always exists)
12 1
23 2
34 3
45 4
56 5
67 6
78 7
7-32
EWA 4NEB 811 6120-02a