Specifications

Position Decoding IP 240
Note
Scratch flags and system data areas are used in the standard function blocks for the
purpose of data interchange with the IP 240 ( Technical Specifications for the
FBs).
You must therefore
save these flags and data areas at the beginning of the service routines for the
S5-115U, S5-135U (when set for interrupt servicing at block boundaries) and
S5-115U (155U mode) and reload them at the end of these routines.
save these flags and data areas at the beginning of the restart (OB21/OB22) of
the S5-135U (with basic setting for the restart mode) and reload them at the
end of these routines.
Technical Specifications
Block number : 170
Block name : STEU. WEG
PLC Library number
Call length/
Block length
CPU
Processing time
1
Function 1234 5
S5-115U P71200-S 5170-D-2 5 words/
975 words
941-7UA...
942-7UA...
943-7UA...
944-7UA...
approx. 38 18 25 80 to 270 28 ms
approx. 20 11 14 30 to 112 15 ms
approx. 14 6.4 8.2 14 to 65 8.2 ms
approx. 3.8 3.3 3.5 5.0 to 18 2.6 ms
941-7UB...
942-7UB...
943-7UB...
944-7UB...
approx. 10.5 6 7.2 11 to 54 7.8 ms
approx. 3.8 3.3 3.5 1.9 to 17 2.2 ms
S5-135U/
S5-155U
P71200-S 9170-D-2 5 words/
1539 words
922 ab A9
928-3UA...
approx. 10 6.6 8.4 19 to 68 9.0 ms
approx. 5.8 3.5 4.4 11 to 45 4.8 ms
928-3UB... approx. 3.1 3.3 3.2 1.7 to 4.0 3.9 ms
S5-150U P71200-S 4170-D-1 5 words/
1508 words
approx. 1.7 1.2 1.4 3.4 to 18 1.5 ms
S5-155U P71200-S 6170-B-1 5 words/
1650 words
946-3UA.../
947-3UA...
approx. 4.3 3.8 4.2 2.7 to 17 2.1
to 3.7 ms
Nesting depth : 0
Subordinate blocks : S5-115U OB160 (only CPUs ...-7UB...)
S5-135U OB122
S5-155U OB91, OB122
Assignments in data area : data block specified with DBNR parameter
up to and including DW 67
Assignments in flag area : MB 240 to 255
System statements : yes
1
The specified processing times are for an FB call following an IP 240 firmware cycle without data interchange. Note
that
when data have been read from the IP 240, further data interchange in the same firmware cycle is disabled.
when new data have been written to the IP 240, further data interchange in the same and in the next cycle is
disabled.
7-24
EWA 4NEB 811 6120-02a