Specifications

C-33
IP 240
EWA 4NEB 811 6120-02b
The LEDs in the front panel allow you to observe the setting of the digital
outputs D1 and D2 on the module.
With the DAV parameter of FC 167, you define the behavior of the digital
outputs of the module at start-up (for example, DAV = 0; outputs control the
traversing speed with separate activation according to D1 = rapid speed and
D2 = creep speed). You define the release of the digital outputs with the con-
trol bits:
DB 168.DBX 72.0 FREE = TRUE,
DB 168.DBX 72.1 MANUAL = FALSE,
DB 168.DBW 38 FUNCTION = B#(20,0).
With brief activation of the input I 1.0 (M 190.0), the control bits are trans-
ferred to the module and become effective immediately. The digital outputs
are set for the duration of the positioning process.
With the control word
DB 168.DBW 38 FUNCTION = B#(20,1)
and by activating the input I 1.0 (M 190.0), the digital outputs are reset re-
gardless of the positioning process.
Setting Digital
Outputs
IP 240 Counter, Position Decoder and Positioning Module