Specifications

Hardware Installation IP 240
Shielding of cable connections on the IP 240
Warning
To ensure noise immunity, shielded twisted-pair cables must be used for all IP 240
connections (inputs, outputs, 24 V power supply).
The following applies to shielding of the connecting cables:
.The cable shields must be placed on a shield
bus near the cable entry in the cabinet.
Braided shields must be secured over as large
an area as possible direct to the shield bus
(for instance with metal cable clamps which
span the shield).
When using cables with foil shields, the
sheath wire incorporated in the shield must
be connected through as short a path as
possible (less than 3 cm) to the shield bus.
The shielding must be extended from the
shield bus to the module.
The shield bus must be conductively
connected to the supporting bar, the cabinet,
and the central grounding point in the
cabinet.
The section entitled ”Installation Guidelines”
in the S5-115U Manual, Edition 2, provides
detailed information on grounding the cable
shields.
Shield bar
Sheath wire
To the module
Cable with foil shield
and sheath wire
Cable with
braided shield
Cable sheath
Braided shield
Foil shield