Specifications
Positioning IP 240
***********************************
SAMPLE PROGRAM FOR S5-135U AND 150U
***********************************
ADDRESS REQUIRED IN PROGRAM DEPENDS ON
PLC TYPE AND DATA BLOCK TYPE:
S5-135U - DB - DF00 HEX
- DX - DE00 HEX
S5-150U - DB - DBBE HEX
======================================================
NAME :L/T DWX
ID :DBNR I/Q/D/B/T/C: D KM/KH/KY/KS/KF/KT/KC/KG: KF
ID :DWNR I/Q/D/B/T/C: I BI/BY/W/D: W
ID :L/T I/Q/D/B/T/C: I BI/BY/W/D: BI
ID :DWN I/Q/D/B/T/C: I BI/BY/W/D: W
ID :DWN1 I/Q/D/B/T/C: I BI/BY/W/D: W
ID :DWN2 I/Q/D/B/T/C: I BI/BY/W/D: W
0017 :K KH DF00 (DF00 FOR DB/135U)
0019 :LW =DBNR (DE00 FOR DX/135U)
001A :+F (DBBE FOR DB/150U)
001B :LIR 1 LOAD ADDRESS OF 1ST DW (DW0)
001C :L =DWNR SOURCE/TARGET DATA WORD NUMBER
001D :+F COMPUTE 1ST DW ADDRESS
001E :A =L/T LOAD/TRANSFER VALUES
001F :JC =TIR
0020 :LIR 3 LOAD ACCUM2 WITH VAL.FROM DW N
0021 :TAK FETCH VALUE IN ACCUM1
0022 :T =DWN OUTPUT VALUE
0023 :TAK LOAD ACCUM1 WITH DW ADDRESS
0024 :ADD BN +1 OFFSET OF +2 TO DW ADDRESS
0025 :LIR 3 LOAD ACCUM2 W. VAL.FRO: DW N+1
0026 :TAK FETCH VALUE IN ACCUM1
0027 :T =DWN1 AND OUTPUT
0028 :TAK .
0029 :ADD BN +1 .
002A :LIR 3 .
002B :TAK
002C :T =DWN2
002D :BEU
002E TIR :L =DWN LOAD VALUE FOR DW N
002F :TAK LOAD DW ADDR. INTO ACCUM1
0030 :TIR 3 TRANSFER VALUE TO DW N
0031 :ADD BN +1 OFFSET OF +2 TO DW ADDRESS
0032 :L =DWN1 LOAD VALUE FOR DW N+1
0033 :TAK LOAD DW ADDR. INTO ACCUM1
0034 :TIR 3 TRANSFER VALUE TO DW N+1
0035 :ADD BN +1 .
0036 :L =DWN2 .
0037 :TAK .
0038 :TIR 3
0039 :BE
10-96
EWA 4NEB 811 6120-02a