Specifications

Counting IP 240
Note
In the standard function blocks, scratch flags and system data areas are used for
data interchange with the IP 240 ( Technical Specifications for the FBs).
You must
save these scratch flags and data areas at the beginning of the interrupt service
routines for the S5-115U and S5-135U (when interrupt servicing after each
statement is enabled) and for the S5-155U (155U mode) and reload them at the
end of these routines.
save these flags and data areas in the restart routines for manual or automatic
restart (OB21/OB22) in the S5-135U (basic setting for restart mode) and S5-
150U and reload them at the end of these routines.
Technical Specifications
Block number : 172
Block name : STEU. DOS
PLC Library number
Call length/
Block length
CPU
Processing time
Function
1234
S5-115U P71200-S 5172-D-2 5 words /
680 words
941-7UA...
942-7UA...
943-7UA...
944-7UA...
approx. 38 18 24 24 ms
approx. 20 10.5 13 13 ms
approx. 12.5 6.2 8.2 7.0ms
approx. 2.8 2.5 2.6 2.7ms
941-7UB...
942-7UB...
943-7UB...
944-7UB...
approx. 11 6.0 7.4 6.0ms
approx. 2.1 1.6 1.9 2.2ms
S5-135U/
S5-155U
P71200-S 9172-D-2 5 words/
1110 Worte
922 from A9
928-3UA...
approx. 10 6.0 7.6 7.0ms
approx. 6.0 3.5 4.2 4.2ms
928-3UB... approx. 2.2 1.8 1.9 2.0ms
S5-150U P71200-S 4172-D-1 5 words/
1054 words
approx
. 1.9 1.2 1.4 1.6ms
S5-155U P71200-S 6172-B-1 5 words/
1311 words
946-3UA.../
947-3UA...
approx. 2.2 1.6 2.0 1.8ms
Nesting depth : 0
Subordinate blocks : S5-115U OB160 (only CPUs ...-7UB...)
S5-135U OB122
S5-155U OB91, OB122
Assignments in data area : data block specified with DBNR parameter up to and
including DW 35
Assignments in flag area : MB 240 to 255
System statements : yes
1
The specified processing times are for an FB call following an IP 240 firmware cycle without data interchange. Note
that
following reading out of data from the IP 240, no further data interchange is possible in the current cycle.
following the writing of new data to the IP 240, no further data interchange is possible in the current or in the
next cycle.
8-12
EWA 4NEB 811 6120-02a