Product manual
IP 266 Troubleshooting
Error Code
Recovery Procedures
Speed range exceeded
Either the override factor is not within the range 1% to 200% or the speed
selected via (valid) override factor exceeds the maximum speed. This error
occurs only in jog modes 1 and 2 and in incremental mode. The positioning
module automatically prevents exceeding of these limiting values.
F87
(Job) orderlist PLC is full
Coincides with error F81, but for the PLC. The last job order must be
reissued.
High-speed change and final block
The selected mode cannot be started because of a "0" signal at the
"external start enable" digital input.
F86
F85
Inadmissible order
The last job order from the PLC or programmer contained either an
undefined mode or was meaningless at this point.
Example: An attempt to start an axis that was already traversing. The
order is ignored.
F82
(Job) orderlist PG is full
Because of the sluggishness of its mechanical parts, the module cannot
process job orders as fast as these can be issued. The last job order issued
via the programmer or PLC is lost, and must be retried.
F81
Block stored
This error is flagged only in mode 10 (TEACH-IN).
F83
F6A Following error out of range
The following error must be in the range 0.001 to 99.999.
F69 Backlash compensation out of range
The backlash compensation value must be in the range 0.001 to
64.999 mm.
Cross-
Reference
Section 5.1.7
Section 5.1.6
Axis operational no inputs possibleF84
Section 5.3.10
Section 2.5.4
Section 5.1.4
EWA 4NEB 812 6057-02
10-11