Product manual
Communication Between the CPU and the IP 266 IP 266
Example:
Assuming you want to operate your drive in mode 1 (JOG 1) with an override
factor of 75%.
Enter the number in byte 3 in binary (KF format).
KF = +75
Set bit 4 in byte 1 to activate the override factor during a traversing movement.
7.1.5 Bytes 4 to 7: Positioning Specifications
A number of IP 266 modes require specification of a position.
This value may be:
• an absolute target position or coordinate (see modes 6 and 12)
or
• a relative position (see modes 7, 13 and 15)
Enter this value in bytes 4 to 7 of the output message as follows:
Table 7-5. Position Specifications
Byte Binary BCD
4
5
6
7
Sign and
integer digits
Sign and the
three highest integer digits
Decimal
digits
First integer digit
and 3 decimal digits
The value can be entered in one of two formats. The value range depends on the
format used:
Binary: ±32767.999
BCD: ± 9999.999
7-8
EWA 4NEB 812 6057-02