Operating Instructions
Chapter 2 – Installing and Configuring the OPC/SNMP Agent
Siemens Building Technologies, Inc. 19
12. In the MIB, find the information for the associated variable, and then identify the Send Trap When
information.
Figure 5. Example of Trap Information Provided with Variable Information.
13. In the Trap dialog box, click Set Trap Conditions.
14. In the Build Condition for Trap dialog box, enter the information to describe trap conditions, and then
click OK.
For example, [FROM] = 0 OR = 1
[TO] = 1 OR = 0
15. In the Trap dialog box, click Set Included Variables.
16. In the Trap Includes dialog box, do the following:
a. Click the name of the Monitoring Variable in the Available Variables box.
b. Click Add.
c. Click OK.
17. In the Trap dialog box, click OK.
The trap is listed in the SNMPEngTool window.
18. Repeat Steps 10 through 17 to add the other traps listed in the MIB.
19. Close the SNMPEngTool window to save the information.