Specifications
Parameters/address space
4.4 Address space
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
20 Manual, 07/2014, A5E03484886-AC
4.4
Address space
The module can be configured differently in STEP 7; see following table. Depending on the
configuration, additional/different addresses are assigned in the process image of the inputs.
Configuration options of AI 8xU/I HS
You can configure the module with STEP 7 (TIA Portal) or with a GSD file.
When you configure the module by means of the GSD file, the configurations are available
under different abbreviations/module names.
The following configurations are possible:
Table 4- 2 Configuration options
Configuration
Short designation/
module name in the
GSD file
Configuration software, e.g., with STEP 7 (TIA Portal)
Integrated in hardware
catalog STEP 7 (TIA Portal)
GSD file in
STEP 7 (TIA Portal)
V12 or higher or
STEP 7 V5.5 SP3 or
higher
1 x 8-channel without value status
AI 8xU/I HS
V12 or higher
X
1 x 8-channel with value status
AI 8xU/I HS QI
V12 or higher
X
8 x 1-channel without value status AI 8xU/I HS S V13 Update 3 or higher
(PROFINET IO only)
X
(PROFINET IO only)
8 x 1-channel with value status AI 8xU/I HS S QI V13 Update 3 or higher
(PROFINET IO only)
X
(PROFINET IO only)
1 x 8-channel with value status for module-
internal shared input with up to 4 submod-
ules
AI 8xU/I HS MSI V13 Update 3 or higher
(PROFINET IO only)
X
(PROFINET IO only)
Value status (Quality Information, QI)
The value status is always activated for the following module names:
● AI 8xU/I HS QI
● AI 8xU/I HS S QI
● AI 8xU/I HS MSI
An additional bit is assigned to each channel for the value status. The value status bit
indicates if the read in digital value is valid. (0 = value is incorrect).