Specifications

Parameters/address space
4.2 Parameters
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
Manual, 07/2014, A5E03484886-AC
17
4.2
Parameters
Parameters of the AI 8xU/I HS
When you assign the module parameters in STEP 7, you use various parameters to specify
the module properties. The following table lists the configurable parameters. The effective
range of the configurable parameters depends on the type of configuration. The following
configurations are possible:
Central operation with a S7-1500 CPU
Distributed operation on PROFINET IO in an ET 200MP system
Distributed operation on PROFIBUS DP in an ET 200MP system
When assigning parameters in the user program, use the WRREC instruction to transfer the
parameters to the module by means of data records; refer to the section Parameter
assignment and structure of the parameter data records (Page 38).
The following parameter settings are possible:
Table 4- 1 Configurable parameters and their defaults
Parameters
Range of values
Default
setting
Parameter as-
signment in RUN
Scope with configuration software, e.g.,
STEP 7 (TIA Portal)
GSD file
PROFINET IO
GSD file
PROFIBUS DP
Diagnostics
Missing supply volt-
age L+
Yes/No No Yes Channel
1)
Module
3)
Overflow
Yes/No No Yes Channel Module
3)
Underflow
Yes/No No Yes Channel Module
3)
Wire break
Yes/No
(Voltage: 1 V to
5 V
Current: 4 mA to
20 mA)
No Yes Channel Module
3)
Current limit for wire
break diagnostics
2)
1.185 mA or
3.6 mA
1.185 mA Yes Channel ---
4)
Measuring
Measuring type
See chapter
Measuring types
and ranges
(Page 16)
Voltage Yes Channel Channel
Measuring range
±10 V Yes Channel Channel
Smoothing
None/low/medium
/high
None Yes Channel Channel
Hardware interrupt
Hardware interrupt
high limit 1
Yes/No No Yes Channel ---
4)