Specifications
Product overview
2.1 Properties
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
Manual, 07/2014, A5E03484886-AC
9
Properties
The module has the following technical properties:
● 8 analog inputs
● Voltage or current measuring type can be set per channel
● Resolution 16 bits including sign
● Configurable diagnostics (per channel)
● Hardware interrupt on limit violation can be set per channel (two low and two high limits
per channel)
● High-speed update of measured values
The module supports the following functions:
Table 2- 1 Version dependencies of the module functions
Function
Firmware version
of the module
Configuration software
STEP 7
(TIA Portal)
GSD file in STEP 7
(TIA Portal) V12 or higher, or
STEP 7 V5.5 SP3 or higher
Firmware update
V1.0.0 or higher
V12 or higher
X
Identification data I&M0 to I&M3
V1.0.0 or higher
V12 or higher
X
Parameter assignment in RUN
V1.0.0 or higher
V12 or higher
X
Isochronous mode
V1.0.0 or higher
V12 or higher
---
Calibration in runtime
V1.0.0 or higher
V12 or higher
X
Module-internal Shared Input (MSI) V2.0.0 or higher V13 Update 3 or
higher
(PROFINET IO
only)
X
(PROFINET IO only)
Configurable submodules / submodules for
Shared Device
V2.0.0 or higher V13 Update 3 or
higher
(PROFINET IO
only)
X
(PROFINET IO only)
Configurable after interface module
IM 155-5 DP ST
V2.0.0 or higher V13 or higher X
You can configure the module with STEP 7 (TIA Portal) and with a GSD file.