Specifications

Product overview
2.1 Properties
Analog Input Module AI 8xU/I HS (6ES7531-7NF10-0AB0)
Manual, 07/2014, A5E03484886-AC
9
Properties
The module has the following technical properties:
8 analog inputs
Voltage or current measuring type can be set per channel
Resolution 16 bits including sign
Configurable diagnostics (per channel)
Hardware interrupt on limit violation can be set per channel (two low and two high limits
per channel)
High-speed update of measured values
The module supports the following functions:
Table 2- 1 Version dependencies of the module functions
Function
Firmware version
of the module
Configuration software
STEP 7
(TIA Portal)
GSD file in STEP 7
(TIA Portal) V12 or higher, or
STEP 7 V5.5 SP3 or higher
Firmware update
V1.0.0 or higher
V12 or higher
X
Identification data I&M0 to I&M3
V1.0.0 or higher
V12 or higher
X
Parameter assignment in RUN
V1.0.0 or higher
V12 or higher
X
Isochronous mode
V1.0.0 or higher
V12 or higher
---
Calibration in runtime
V1.0.0 or higher
V12 or higher
X
Module-internal Shared Input (MSI) V2.0.0 or higher V13 Update 3 or
higher
(PROFINET IO
only)
X
(PROFINET IO only)
Configurable submodules / submodules for
Shared Device
V2.0.0 or higher V13 Update 3 or
higher
(PROFINET IO
only)
X
(PROFINET IO only)
Configurable after interface module
IM 155-5 DP ST
V2.0.0 or higher V13 or higher X
You can configure the module with STEP 7 (TIA Portal) and with a GSD file.