4 Hardware components
4.1 Room automation – Room controller unit
(RCU)
The room controller unit (RCU) is assigned the most important functions within the
integrated system. It communicates both with the connected peripheral devices in
the guest rooms as well as directly with the HRMS management station at the
reception desk.
All important room parameters can no longer be lost after system commissioning
and configuration and are autonomously stored in the controller. This guarantees
full functionality of all local room functions even without a network connection.
Two room control units are available for Hotel Solution:
HRC3.1 – for expanded requirements (Advanced)
HRC3.2 – for standard requirements (Standard)
HVAC, lighting, blinds, access
Standard Advanced
Proprietary (KNX)
HRC3.2
HRC3.1
Room controller HRC3.2 HRC3.1
Power supply
Power
AC 24 V AC 24 V
Consumption (without consumer on the relay)
Max. 1.25 A Max. 1.5 A
Inputs/outputs
Digital inputs DC 12V / 5mA (no electrical isolation) 8 16
Analog inputs For LG-Ni 1000 0 1
Relay outputs 230 V voltage free 7 8
Relay outputs 230 V powered 4 0
Relay outputs 24 V powered 0 6
Triac outputs AC 24 V 4 0
Output door opener DC 12 V 1 1
Output door opener AC 24 V 0 1
Digital outputs DC 12 V, powered 0 8
Communication
Room bus RS485 RS485
Konnex bus KNX KNX
Interface for standard room device
PPS2
Dimensions
150 x 110 x 62 mm 284 x 160 x 57 mm
The room controllers are loaded and supplied with pre-configured standard
applications (see 4.2). You can download modified applications for the customer
proje
ct using the HSC Tool via the KNX network.
Function
Product range
Technical data
Applications