Siemens HMI CM2B6307en
Building Technologies Display and operating pages 12/15/2008
3.4 Room Overview.
This HMI page provides the basic data on the room controller.
Parameters Description Can this
field be
edited?
Reader This parameter displays the active, correctly configured and
parameterized card readers on the controller.
1 = Card reader active and without error.
0 = No card reader connected/active or
the wrong address is set on the card reader.
No.
Holder This parameter displays the active, correctly configured and
parameterized card holder on the controller.
1 = Card holder active and without error.
0 = No card holder connected/active or
the wrong address is set on the card reader.
No.
TCU This parameter displays the active, correctly configured and
parameterized room units on the controller.
1 = Room units are active and without error.
0 = No room unit connected/active or
the wrong address is set on the card reader.
Nein
FanSpd Display of the current fan speed. No.
RoomTemp Present room temperature display. No.
Room Stp The present setpoint for the room can be entered here. It is
overwritten, however, when the KNX bus is re-connected.
Yes.
Htg Display of current position of the heating valve. No.
Clg Display of current position of the cooling valve. No.
back Back to Diagnostics page. No.