User Manual
12 / 14 For internal use only
Siemens HMI CM2B6307en
Building Technologies Display and operating pages 12/15/2008
3.6 Switch Outputs
Conducts wiring test at the output. Each output can be switched individually.
The parameter Simulate (Diagnostics page) must be set to Simulation to use this
page.
The outputs are reset when an output is changed using the HMI and simulation is
set to normal operation.
Parameters Description Can this
field be
edited?
Switch RL HRC3.1: Switch on relay RL1-RL8.
HRC3.2: Switch on relay RL1-RL5.
Yes.
Switch RH HRC3.1: Switch on relay RH4-RH9.
HRC3.2: Switch on relay RH4-RH7.
Yes.
Switch DO HRC3.1: Switch on relay DO1-DO8.
HRC3.2: Switch on Triacs Tr1-Tr4.
Yes.
Switch Fan Switch on fan speed 1-3. Yes.
back Back to Diagnostics page. No.