User Manual

37
Siemens Switzerland Ltd
Building Technologies Division
always require a site-specific design, as all pipe diameters and nozzles must be
calculated individually according to the particular application.
Modular systems, on the other hand, consist of space-saving compact units that
are installed within the protection zone itself. These units combine fast and
reliable detection with quiet and safe extinguishing in one compact package.
They are particularly suitable for the protection of small enclosures with volumes
up to 120 m
3
that contain electronic and electrical equipment. The main cost-
saving advantage of such systems is that they can be installed quickly and easily,
and service and maintenance costs are very low.
Figure 4.4.2-1 Modular and centralized extinguishing system
Kitchens The fire risk in kitchens is relatively high. This is due to a combination of the
cooking materials used (cooking oils, fats, etc.) and the hot cooking equipment
(hot-plates, ovens, vats, etc.). Kitchen fires are predominantly fat fires, which
often start spontaneously and rapidly generate an intense heat. The flames are
also fed by the highly combustible fat vapors and can only be checked by
interrupting the oxygen supply and reducing the temperature of the cooking oil.
An additional problem related to kitchen fires is their inherent ability to spread
through the kitchen’s own air extraction system to the rest of the building. The
critical areas (e.g. cooking range, deep fat fryers, ovens and air extraction
system) should be protected by specially designed extinguishing systems. Wet
chemical fire extinguishers (Class F) should also be provided.
When extinguishing systems are used in commercial kitchens, then these are wet
chemical systems, which are installed immediately above the protection area or
within the air extraction hoods. They are stand-alone systems, which both detect
the fire and extinguish it automatically. The effectiveness of this extinguishing
agent relies on the cooling of the hot surfaces together with a highly efficient fire
suppression mechanism. On contact with the hot fat, the extinguishing agent
foams up to produce a soapy layer. This creates a dense barrier between the hot
fat and the surrounding air, effectively preventing the highly volatile fat vapors
from escaping and reigniting the fire.
If the hotel is equipped with a sprinkler system, then this should be extended to
protect the other parts of the kitchen. However, it must be ensured that the
water spray from the sprinklers cannot reach the critical areas of the cooking
range, deep fat fryers, ovens and air extraction system.