Data Sheet for Product
4/6
Siemens HTR3.1/B – Transponder card reader CM2N6337en
Building Technologies 01.12.2008
Engineering notes
The HTR3.1/B transponder card reader is designed for flush wall mounting, and for
fixing purposes is installed in a type AZ26.x base frame (where x = 1…4). Cover plates
for this base frame are available from the installation ranges of various manufacturers
(see "Ordering").
Up to four card readers can be connected to the same room bus.
The address is set by means of pushbutton on the rear of the device (see below).
The maximum permitted current associated with the supply voltage from the HRC3..
room controller must not be exceeded.
Refer to data sheets N6313, N6314
Mounting
• The HTR3.1/B transponder card reader must be mounted in the entrance lobby of
the hotel room at the same height as the light switch.
• Ensure that there is sufficient spare cable in the mounting box to allow access to the
pushbutton on the back, for the programming of addresses.
• The device is intended for fixed installation in a dry, enclosed space.
• For three modules, the mounting box must be installed at a depth of 47.5 mm
• Mount horizontally only, with the front plate vertical
• Do not install AC 230 V devices in the same mounting box
• Commissioning must be carried out by trained personnel only
• Do not open the unit
• Local safety and installation regulations must be observed
Commissioning
The address can be set by means of pushbutton on the rear of the device:
1. Connect the device to the room controller
2. To activate programming mode, use a small screwdriver to hold the pushbutton
down for 3 seconds:
All the LEDs will then light up to indicate programming mode.
3. Pressing the button briefly changes the address one step at a time, allowing you to
cycle through the addresses shown below
4. Hold the pushbutton down for 3 seconds again to save the address.
The new address is saved in the non-volatile area of the memory.
All LEDs will then switch off.
The addresses are indicated in code form by the following LED sequences:
Bus address LED 1 LED 2 LED 3
Ready for programming ON ON ON
0x38 ON OFF OFF
0x39 OFF ON OFF
0x3A OFF OFF ON
0x3B ON ON OFF
In the standard application with only one reader, Address 0x38 is intended for the
HTR3.1/B transponder card reader.
This address is factory-set in the HTH3.1/B transponder card reader.
Other information
Note