The setpoints are assigned as follows:
Room state Temperature profile Setpoint Heating strategy
Comfort
Winter 22 °C Heating only
Standby A
Winter 19 °C Heating only
Standby B
Winter 17 °C Heating only
Standby C
Winter 13 °C Heating only
The temperature profile Winter is activated via System | Temperature
Profiles...
In this case, the room state must not be set by default to Standby C when a
guest checks out. For this reason you should check that the entry
"default_room_state" under System | Configuration Parameters... is set to
Comfort or Standby A.