Data Sheet for Product

Application
The HRC3.1 room controller integrates temperature control, energy management,
access control and the management of a hotel room, at room level.
For operation, room operator units, access card readers and access card holders with
bus connection and switch e.g. to turn on the lights are used.
Functions
The functions are determined by the downloadable application software. The room
controllers are delivered with the standard application (the basic features are described
in this data sheet).
In special cases, the standard application can be overwritten with a customized
application software. A commissioning and service tool is available for this purpose.
The following options can be implemented with fan-coil units: Temperature control
4-pipe heating/cooling with 3-position or PWM output
2-pipe heating/cooling with 3-position or PWM output with changeover
2-pipe system with internal electric heating, 2-position or PWM output, and cooling
with 3-position or PWM output
2-pipe system with external electric heating, 2-position or PWM output, and cooling
with 3-position or PWM output
4-pipe heating via external radiator and cooling with 3-position or PWM output
Auxiliary heating in bathroom, additional radiator or underfloor heating with
2-position, 3-position or PWM output
Room temperature setpoints:
Centrally programmable room comfort temperature setpoint
Individual setpoint adjustment of room comfort room temperature setpoint in guest's
room
Precomfort setpoints when guest is absent
Economy setpoints for free rooms (i.e. from which guests have checked out)
Remote room temperature setpoint adjustment in rooms unoccupied for long periods
Energy-saving features:
Energy management for individual room control system and lighting
based on room occupancy
Summer/winter strategy
(i.e. avoid heating in summer and avoid cooling in winter)
Fan disabled if window is opened
Electricity:
Energy management
Master switch function: to switch electrical consumers on and off
Switch-on control of courtesy light function upon entry to room
Electrical consumers enabled and disabled by pre-programmed guest-dependent or
hotel-staff dependent function
Water supply shut off in absence of guest or hotel staff (only possible with magnetic
valve installed)
Control of blinds or curtain
Receipt of access code from the connected magnetic, chip, or transponder card
reader
Access control
Control of access to guest rooms, suites and general access areas
Receipt of access codes for guests, hotel staff and emergency access cards from
the central management station at the reception
Management of all access codes
Activation of door opening mechanism when access is granted
2/12
Siemens HRC3.1 – Room controller CM2N6313en
Building Technologies 01.09.2008