Data Sheet for Product

1 DO 5 Auxiliary heating control (on/off, PWM, 3-position open)
2 DO 6 Auxiliary heating control (on/off, PWM, 3-position closed)
3 DO 7 FNC03 electric reheater output (PWM)
4 DO 8 A time scheduler may be programmed
5 GND
Connector X8
Digital outputs
DC 1 V, max. 80 mA
1 DI 1 ON/OFF button for main switch, RH7
2 DI 2 "Room service“ or "Please clean room" button
3 DI 3 "Do not disturb" button
4 DI 4 "SOS Call"
5 GND
6 DI 5 "Blinds UP" button
7 DI 6 "Blinds DOWN" button
8 GND
9 DI 7 Window monitoring contact: window
10 DI 8
"Bell" button
11
DI 9 Card-holder contact: contact closed = person in room
12 GND
Connector X9
Digital inputs
DC 12 V / 5 mA
1 DI 10
ON/OFF button for main switch RH7
2 DI 11
ON/OFF button for main switch RH7
3 DI 12 Switch or pulse contact for RH9, if no light scenario is programmed
4 DI 13 Minibar contact: door closed = contact closed
5 DI 14
ON/OFF button for RH6
6 GND
7 DI 15
Door monitoring contact: door closed = contact closed
8 DI 16
Button for door-o
p
enin
g
mechanism
9 GND
10 AI 1
Ni1000 temperature sensor
11 +12V
Output voltage
12 GND
Connector X10
Digital inputs
DC 12 V / 5 mA
1
CP+ PPS2, Data
2
CP– PPS2, GND
3
CE+ (galvanically separated from room controller)
4 CE– (galvanically separated from room controller)
Connector X11
PPS2 interface and
Konnex building bus
1 A+ RS485
2 B– RS485
3 DC +12V, max. 500 mA
4 GND
Connector X12
Room bus
STOP
Caution
Fans connected to the relay outputs must not be operated in parallel.
For parallel operation use cut-off relays or slave room controllers.
11/12
Siemens HRC3.1 – Room controller CM2N6313en
Building Technologies 01.09.2008