Data Sheet for Product

Operating notes
Pattern Description
All symbols OFF
No supply voltage to the HTC3.2
Possible causes:
Room controller off or faulty
Bus cable not correctly connected, or connection broken
HTC3.2 faulty
All symbols
flashing (2 Hz)
No communication with the room controller
Possible causes:
Wrong bus address set on HTC3.2
Wrong bus address set in room controller
Bus cable not correctly connected, or connection broken
Room controller in "Stop" mode
Faulty RS485 interface
Alarm messages
Technical data
Operating voltage DC 9..0.15 V
Power supply (from HRC3..)
Current 20 mA
Bus interface Bus voltage SELV DC 12 V
Type RS485
Transmission speed 4800 baud
Temperature signal input Measuring range 5 … 45 °C
Measuring current
1 mA
Measuring element NTC 10 k
Setpoint correction Correction range ± 2 or ± 4 K
Resolution 0.5 K or 1 K
Parameter setting Parameters set with internal software and
stored in EEPROM
Ambient conditions Operating temperature 0...+ 50 °C
Transport temperature
-25..+ 65 °C
Humidity <95 % non-condensing
Air pressure during operation Min. 700 hPa (3000 m above sea level)
Air pressure during transport Min. 260 hPa (10 000 m above sea
level)
Industry standards
Product safety
Automatic electrical controls for household
and similar use
EN 60 730-1
Electromagnetic
compatibility
Emitted interference in accordance with
Interference immunity in accordance with
EN 61000-6-3
EN 61000-6-2
Housing
protection standard
To EN 60,529
IP20
Protection class To IEC1140 III
conformity Meets the requirements of:
EMC Directive
89/ 336 / EEC
Low-voltage directive 73/23/EEC
Environmental
compatibility
Environmental product declaration
CM2E6320en provides data on
environmentally compatible product design
and assessment (material composition,
packaging, disposal)
ISO 14001 (environment)
ISO 9001 (quality)
UL/CUL approval UL/CUL 916
8/10
Building Technologies HTC3.2/.. - Room operator unit CM2N6320en
01.09.2008