Data Sheet for Product
5/14
Siem ens HRC3.2 – Room controller CM2N6314en
Building Technologies 2016-12-23
A plug-in terminal is provided for the commissioning and service tool.
All other terminals are fixed.
To avoid incorrect wiring, terminals which can be connected to AC 230 V (supply and
relay outputs) are physically segregated from the other terminals. They are arranged so
that, under normal circumstances, all incoming and outgoing cables can be connected
without crossing.
STOP
Caution
Cable restraints must be used for the wires to terminal
blocks X4 and X5 (AC 230 V).
The conductors must be secured with cable ties (see
diagram, right).
6314z0 5
The red / green service LED displays the operating status for the room controller. The
viewer see the color orange when the red and green LEDs are on at the same time.
The service LED states are as follows:
LED display Operating state
Red blinking: Blinking
frequency 0.1 second on,
1 second off,
Green off
Operating system running; no measuring and control
task is loaded
Red blinking: Blinking
frequency 0.1 second on,
0.1 second off
Green on
Operating system running; measuring and control task
loaded and in STOP
Red off
Green blinking
Operating system running; measuring and control task
loaded and in RUN
· The blinking frequency is the same as the cycle
time for the measuring and control task
Red on
Green blinking
Operating system running; measuring and control task
loaded and in RUN
· Addressing mode is on: The blinking frequency is
the same as the cycle time for the measuring and
control tasks
· Address mode is off: Error
Red off
Green off
· No power
· Error
· If the management system or communication link fails, this will not affect local
operation
· External fuses are required for the relay contacts
· The controller comes with a self-resetting thermal fuse to prevent overload damage.
Disposal
The devices are considered electronics devices for disposal in terms of European
Directive 2012/19/EU and may not be disposed of as domestic garbage.
· Dispose of the devices through channels provided for this purpose.
· Comply with all local and currently applicable laws and regulations.
Service LED
Response in the event
of a fault