User Manual
8/14
Building Technologies RXC34.1/ALG – Controller with LonWorks® interface CM2N3848en_02
12.01.2007
Analog outputs Number
Output voltage
Linearity error
Offset error
Gain error
Resolution
Load current
Setting time
Protective circuit
8 (AA1...AA8)
DC 0...10 V, non-floating
± 2 bits = 20 mV
0.5 %
± 0.5 %
10 bits
5 mA
Approx.
Up to 24 V without interference
Ports/interfaces
Field-device interfaces
Serial interface
Interface for external extension modules
X1…X12, Wago cage-clamp plug-in
connectors at
X13, RJ45 socket, 8-pin
Sub-D, 9-pin male
L
ONWORKS® bus
Medium
Transceiver
Baud rate
Bus topology, bus termination
L
ONMARK®-compatible,
electrically isolated
TP/FT-10
FTT-10A
78 kbit/s
See Installation guide, CA110334
Housing protection
Protection standard to EN 60529 IP20
Protection class
Humidity class
F to DIN 40040
Ambient conditions
Air pressure Normal operation
Transport
Min. 700 hPa, equivalent to max.
3000 m above sea level
Min. 260 hPa, equivalent to max.
10,000 m above sea level
Temperature
Operation
Storage
–10...+50 °C
–30...+70 °C
Industry standards
Mechanical strength
EMC measurement
Vibration and shock testing
Environmental testing
Storage temperature
Humidity test
Temperature test
DIN IEC 68-2-32
EN 61000-6-1; EN 61000-6-3
EN 60068-2-27/31/32
EN 60068-2-14
EN 60068-2-1/2
DIN IEC 60068-2-30
EN 60068-2-14
Dimensions
W x H x D
284 mm x 158 mm x 54 mm
Width in DIN modular spacing units
16
General data
Mounting methods EN 50022 DIN-rail, 37 x 7.5 mm
Color
RAL 7016, anthracite gray
Weight
Excluding packaging 1.35 kg