User Manual
6/14
Building Technologies RXC34.1/ALG – Controller with LonWorks® interface CM2N3848en_02
12.01.2007
• The outputs generate voltages from DC 0 .. +10 V
• Maximum load current 5 mA
• 10-bit resolution
• The outputs are short-circuit-proof
• The outputs are non-floating
• Protective circuit: immunity up to +24 V
• Maximum load impedance: 2 kΩ
Owing to the use of cage-clamp terminals, the cross-section of the connecting cables
must not exceed 1.5mm
2
.
• All signal cables must be screened
• Every analog input connection should be a twisted pair.
• The conductor screen must be connected to a shield bus, ensuring good surface
contact, prior to the RXC34.1/ALG connection.
The RXC34.1/ALG housing incorporates four LEDs for status indication.
LED Color Operating state
Normal operation Application terminated
CTRL (LED1)
Green Flashing OFF
FAULT (LED2) Red OFF OFF
COM (LED3) Green OFF ON
OK (LED4) Green Fast flashing Fast flashing
Commissioning
The RXC34.1/ALG controller is commissioned with the RXT10 commissioning and
service tool. This tool is connected to the L
ONWORKS® bus.
The L
ONWORKS® bus can be connected and reconnected whenever necessary, without
switching off the power.
STOP
Caution
There is no protection against the accidental connection of AC 230 V on the
AC 24 V side.
Conductor cross-
section
EMC precautions
Status LEDs
Note
.
.
.
.
.