User Manual
11/14
Building Technologies RXC34.1/ALG – Controller with LonWorks® interface CM2N3848en_02
12.01.2007
Analog outputs
X9 and X10
Each pair of analog outputs has a common ground (NOT G0!).
(e.g. terminal X9.3 is ground for X9.1 and X9.2).
Connecting terminals 3 or 5 to G0 will damage the printed circuit board!
123456
X9 X10
3848V04
+ + - + + - + + - + + -
SP
SN
GG0Y
123456
Analog outputs
Rotary actuator AC 24 V
DC 0 ..10 V input
Universal inputs
X11/X12
with passive sensor
123456
X11
3848V05
7 8 9 10111213 14
+ - + - + - + - + - + - + -
Universal inputs
Pt1000, Pt100 or LG-Ni 1000
temperature sensor
(LAB applications: LG-Ni1000 only)
Universal inputs
X11/X12
with active sensor
voltage
123456
X11
3848V08
7891011121314
+ - + - + - + - + - + - + -
SP
SN
GMB
Universal inputs
Active sensor with DC 0 .. 10 V
output signal
Universal inputs
X11/X12
with signal contact
123456
X11
7 8 9 1011121314
+ - + - + - + - + - + - + -
3848V09
Universal inputs
Digital signal sources