Installation Instructions

Document No. A5W00070317
Installation Instructions
November 9, 2020
Siemens Industry, Inc. Page 3 of 5
Wiring
NOTE: All wiring must conform to NEC and local codes and regulations.
24 Vac/dc
Function
Color
Supply
Red
Neutral
Black
Ground
Green/Yellow
120 Vac
Function
Color
Line
Black
Neutral
White
Ground
Green/Yellow
230 Vac
Function
Color
Line
Brown
Neutral
Blue
Ground
Green/Yellow
CAUTION:
These AC powered actuators must be wired with
Line referenced with respect to Neutral, as
indicated. The ground lead must be connected for
proper protection of the actuator. Any other
connection, such as phase-to-phase, can damage the
actuator.
Switch
Wire
Color
Switch
Makes
Switch
Breaks
Gray
< 5°
>
85°
Yellow
> 85°
< 85°
Fixed Dual End Switches.
NOTE:
Both sets of contacts are open when actuator
is between 5° and 85°.
CAUTION:
Mixed switch operation to the switching outputs
of both fixed dual end switches (5° and 85°) is
not permitted.
Either AC line voltage from the same phase
must be applied to all four outputs of the fixed
dual end switches, or UL-Class 2 voltage must
be applied to all four outputs.