Data Sheet for Product
Table Of Contents
3 / 10
Siemens Air damper actuators GQD...1 CE2N4604en
Smart Infrastructure 2021-09-07
transformer (100% duty cycle)
EN 61 558
Fuse for incoming supply line (fast)
2 A
Operating voltage / Frequency
AC 230 V ± 15%; 50 / 60 Hz
Fuse for incoming supply line (fast)
2 A
Power consumption
GQD321.1A / GQD
326.1A: (running)
(holding)
10 VA / 4.5 W
7 VA / 3 W
Nominal torque
2 Nm
Maximum torque
6 Nm
Nominal rotational angle
90°
Maximum rotational angle
(mechanically limited)
95 ± 2°
Runtime at nominal rotational angle 90°
30 s
Closing
time with spring return
(on power failure)
15 s
Duty cycle
100%
Direction of rotation
Clockwise/counter-clockwise
Mechanical life
60 000 cycles
Contact voltage
Contact current
AC 24 V / DC 24…48 V
or A
C 0 V
8 mA typical
Input voltage Y (max.)
Working range Y
DC 0…35 V
DC 0…10 V
AC power
−
Switching voltage
−
Rated voltage resistive / inductive
No mixed operation AC 24 V / 230 V
DC power
−
Switching voltage
−
Rated current
Factory switch setting
−
Switch A (set)
− Switch B (set)
AC 24...230 V
6 A / 2 A
DC 12…30 V
DC 2 A
5°
85°
Cable length
0.9 m
Cross-section
0.75 mm
2
Protection as per EN 60 529
IP40
Insulation protective class
−
AC 230 V
− AC/DC 24 V
EN 60 730
Operation
−
Climatic conditions
−
Mounting location
−
Temperature (extended)
− Humidity, non-condensing
IEC 721
-3-3
Class 3K5
Interior, weather
-protected
-
32...+55 °C
< r.h. 95%
Transportation
−
Climatic conditions
−
Temperature (extended)
− Humidity, non-condensing
IEC 721
-3-2
Class 2K3
-
32…+70 °C
< 95% r.h.
Storage
−
Climatic conditions
−
Temperature (extended)
− Humidity, non-condensing
IEC 721
-3-1
Class 1K3
-
32…+50 °C
< 95% r.h.
Mechanical conditions
Class 2M2
Supply voltage
AC 230 V
Functional data
Positioning signal for
GQD131.1A / GQD136.1A
Positioning signal for
GQD161.1A / GQD166.1A
Auxiliary switch
Connection cables
Housing type
Protection class
Environmental conditions