4 604 OpenAir™ GQD...1 Air damper actuators Rotary version, AC/DC 24 V and AC 230 V GQD…1 CE2N4604en 2021-09-07 • Electric motor-driven actuators for two-position and three-position control as well as DC 0…10 V control • 2 Nm nominal torque • AC/DC 24 V or AC 230 V rated voltage • Prewired with 0.
Use • For damper areas up to 0.3 m2, friction dependent. • For directly driven zone dampers to control air flow in air ducts. Type summary Spring return rotary actuators GQD Type GQD121.1A GQD126.1A GQD321.1A GQD326.1A GQD131.1A GQD136.1A GQD161.1A GQD166.1A Operating voltage AC/DC 24 V AC/DC 24 V AC 230 V AC 230 V AC 24 V / DC 24…48 V AC 24 V / DC 24…48 V AC 24 V / DC 24…48 V AC 24 V / DC 24…48 V Control signal 2-position 2-position 2-position 2-position Cable length 0.9 m 0.9 m 0.9 m 0.
Supply voltage AC 230 V Functional data Positioning signal for GQD131.1A / GQD136.1A Positioning signal for GQD161.1A / GQD166.1A Auxiliary switch Connection cables Housing type Protection class Environmental conditions transformer (100% duty cycle) Fuse for incoming supply line (fast) Operating voltage / Frequency Fuse for incoming supply line (fast) Power consumption GQD321.1A / GQD326.
Standards Product safety Automatic electrical controls for household and similar use Electromagnetic compatibility (Application) EU Conformity (CE) RCM Conformity Product environmental declaration 2) Actuator W×H×D Damper shaft − Rectangular Min. length Max. shaft hardness − Round Min. length Max. shaft hardness Excl. packaging − GQD121.1A − GQD126.1A − GQD321.1A − GQD326.1A − GQD131.1A − GQD136.1A − GQD161.1A − GQD166.
Engineering notes STOP This section explains general and system-specific regulations for mains and operating voltages. It also contains important information on your own safety and that of your plant. Intended use Use these actuators as described in the basic system documentation for the applied control systems.
Wiring and commissioning Refer to the sections “Commissioning notes” and “Wiring diagrams” in this data sheet as well as to the HVAC job drawings. Mounting notes Mounting instructions All information and steps to properly prepare and mount the actuator are listed in the mounting instructions supplied with the actuator. Mounting position Mount the actuator in a position which ensures easy access to the cables and to the shaft adapter. See "Dimensions”.
GQD131.1A GQD136.1A Power supply AC 24 V / DC 24…48 V wires red (1), black (2) Positioning signal AC 24 V / DC 24…48 V or AC 0 V • Wire violet (6) ON: Actuator turns clockwise • Wire orange (7) ON: Actuator turns counter-clockwise • Wire violet (6) and wire orange (7) ON: Actuator turns counter-clockwise • Wire violet (6) and wire orange (7) OFF: Actuator stops • Supply OFF: Actuator runs counter-clockwise (mechanical, via spring) GQD161.1A GQD166.
AC 24...230 V / 6 (2) A DC 12...30 V / 2 A S1 S4 1 8 S1 (Q21) G Y (Q11) 1) S5 S6 GD..1E_Z12 Connection GQD121.1A GQD126.1A AC/DC 24 V GQD321.1A GQD326.1A AC 230 V GQD131.1A GQD136.1A AC 24 V DC 24…48 V GQD161.1A GQD166.1A AC 24 V DC 24…48 V Aux. switch 1) 9 S2 S3 (Q24) U 2 (Q22) (Q14) G0 AC/DC 0 V 1) Cable labeling S4 0% 4604G03a (Q24) S2 S3 100% M (Q22) 2 AC 24 V AC/DC 0 V DC 24...48 V (Q14) G0 (Q12) M 1 AC 24...230 V / 6 (2) A DC 12...30 V / 2 A DC 0...
Dimensions 9 / 10 Siemens Smart Infrastructure Air damper actuators GQD...
Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724-2424 www.siemens.com/buildingtechnologies © Siemens Switzerland Ltd, 2010 Technical specifications and availability subject to change without notice. 10 / 10 Siemens Smart Infrastructure Air damper actuators GQD...