Data Sheet for Product

2 / 10
Siemens A6V10636100_en--_d
Building Technologies 2018-04-09
Features
The spring return actuator drives the damper to the desired operating position after
connecting the operating voltage. At the same time, the spring return, integrated in the
actuator, is tensioned. In the event of a loss of operational voltage, the spring return auto-
matically drives the damper to the defined emergency position.
Brushless, robust DC motors ensure reliable operation regardless of load.
The damper actuators do not require an end position switch, are overload proof, and
remain in place upon reaching the end stop.
The gears are maintenance free and low noise.
Simple and reliable shaft fixation.
Mounting bracket included.
The spring preload of 5° ensures safe closure of the air dampers.
Use
Rotary actuator with spring return. Used on ventilation and air conditioning plants to
operate air dampers that must be rotated to a defined emergency position during a power
outage.
For damper areas up to 0.6 m
2
, friction dependent.
Suitable for use with modulating controllers (DC 0/2...10 V), open-close or three-position
controllers.
For directly driven zone dampers to control air flow in air ducts.
We recommend a minimum pulse length of 500 ms on rotary actuators operated with
3-point control to ensure continuous and accurate operation.
Functions
Type
AC 24 V ~ /
DC 24…48 V
GPC12..1A GPC13..1A GPC16..1A
AC 100…240 V ~ GPC32..1A GPC361.1A
Control type Open-close Three-position Modulating control
Rotary direction Clockwise (cw) or counter-clockwise (ccw) direction depends
on the mounting position on the damper shaft …
… on the type of control. ... on the type of control
on the setting of the rotary
direction DIL switch (cw / ccw)
Emergency function In the event of a power outage or switching off operating voltage, the spring return
drives the actuator and damper, connected by the damper shaft, to the defined
emergency position.
Position indication:
Mechanical
Rotary angle position indication by a position indicator.
Position indication:
Electrical
Output voltage U = DC 0/2...10 V
is generated proportional to
the rotary angle.
U depends on the rotary
direction of the DIL switch
setting.
Auxiliary switches Fixed position 5° / 85°