s OpenAir™ Air damper actuators with spring return GPC..1A Electric motor-driven rotary actuators for open-close, three-position and modulating control ● ● ● ● ● ● 4 Nm nominal torque Operating voltage AC 24 V ~ / DC 24…48 V ⎓ or AC 100…240 V ~ Emergency function with spring return Prewired with 0.
Features The spring return actuator drives the damper to the desired operating position after connecting the operating voltage. At the same time, the spring return, integrated in the actuator, is tensioned. In the event of a loss of operational voltage, the spring return automatically drives the damper to the defined emergency position. ● Brushless, robust DC motors ensure reliable operation regardless of load.
Technical design/mechanical design Housing The housing consists essentially of flame retardant, non brominated, non chlorinated glass fibre reinforced plastic. Type summary Typ Stock number GPC121.1A S55499-D233 GPC126.1A S55499-D234 GPC131.1A S55499-D235 GPC136.1A S55499-D236 GPC161.1A S55499-D237 GPC166.1A S55499-D238 GPC321.1A S55499-D239 GPC326.1A S55499-D240 GPC361.1A S55499-D241 Control Operating voltage Position indicator U = DC 0/2…10 V Aux.
Installation WARNING No internal line protection for supply lines to external consumers Risk of fire and injury due to short-circuits ● Adapt the line diameters as per local regulations to the rated value of the installed fuse. Maintenance The rotary actuators with spring return GPC..1A are maintenance-free. Disposal The device is considered electrical and electronic equipment for disposal in terms of the applicable European Directive and may not be disposed of as domestic garbage.
Inputs Positioning signal for GPC12..1A Operating voltage AC 24 V ~ / DC 24…48 V ⎓ / 0 V (wires 1-2/G-G0) open / close Positioning signal for GPC32..1A Operating voltage AC 100…240 V ~ (wires 3-4/L-N) open / close Positioning signal for GPC13..1A Operating voltage AC 24 V ~ / DC 24…48 V ⎓ Switching current (wires 1-6/G-Y1) (wires 1-7/G-Y2) open close typically 8 mA (wires 8-2/Y-G0) DC 0/2…10 V ⎓ 0.1 mA >100 kς DC 35 V Positioning signal for GPC16..1.
Standards, directives and approvals Product standard EN 60730 Part 2-14 / Particular requirements for electric actuators Electromagnetic compatibility (Applications) For use in residential, commerce, light-industrial and industrial environments EU Conformity (CE) A5W00029693 2) RCM Conformity A5W00029694 2) EAC Conformity Eurasian conformity UL UL 1) cUL according UL 60730 http://ul.com/database 2) according CSA-C22.2 No.
GPC13..1A (Three-position) AC 24 V ~ / DC 24…48 V ⎓ III AC 24 V ~ DC 24...48 V AC 24...250 V ~ / 6 (2) A DC 12...30 V / 2 A 1 S4 (Q11) (Q21) S1 GPC16..1A 7 (Q24) S5 S6 S2 S3 GPC361.1A (Modulating control) AC 24 V ~ / DC 24…48 V ⎓ AC 24 V ~ DC 24...48 V SELV/PELV DC 24 V DC 0/2...10 V AC 24...250 V ~ / 6 (2) A DC 12...30 V / 2 A AC 100...240 V ~ 3 8 100% M 1 8 (Q21) 1 DC 0/2...
GPC3..1A (AC 100…240 V ~) Open-close control Modulating control AC 100...240 V ~ AC 100...240 V ~ L L G+ N N G- Y U N Cable labeling Connection Cable Meaning Code No. Color Abbreviation Actuators G 1 red RD System potential AC 24 V ~ / DC 24…48 V ⎓ AC 24 V ~ G0 Y1 2 6 black purple BK VT Y2 7 orange OG System neutral Pos. signal AC/DC 0 V, AC 24 V ~ / DC 24…48 V ⎓, "open" (GPC13..1A) Pos. signal AC/DC 0 V, AC 24 V ~ / DC 24…48 V ⎓, "close" (GPC13..
ø 6.9 GPC..1A_M01 ø 6.9 ø 8.
Issued by Siemens Switzerland Ltd Building Technologies Division International Headquarters Theilerstrasse 1a 6300 Zug Switzerland Tel. +41 58-724 24 24 www.siemens.com/buildingtechnologies Document ID A6V10636100_en--_d Issue 2018-04-09 © Siemens Switzerland Ltd, 2015 Technical specifications and availability subject to change without notice.